Rockwell Automation SA500 Drive Configuration and Programming User Manual
Page 75
Configuring the UDC Module’s Registers
3-43
3.7
UDC Module Test I/O Registers (Registers 1000-1017)
This view is used to configure the UDC module’s Test Switch Inputs Register and the
Meter Port Setup Registers.
3.7.1 UDC Module Test Switch Inputs Register (Register 1000)
This view is used to configure the register that displays the status of the test switches
and LED indicators on the UDC module. Writing to this register will not change the
state of the LEDs. The status of this register is retained during a Stop All.
UDC Test Switch Inputs Register
1000
UDC Push-button
Bit 0
The UDC Push-button bit is on when the
UDC’s push-button is pressed.
Hex Value:
0001H
Sug. Var. Name:
UDC_PB@
Access:
Read only
UDC Error Code: N/A
LED:
N/A
UDC Switch Up
Bit 1
The UDC Switch Up bit is on when the test
switch is in the up position.
Hex Value:
0002H
Sug. Var. Name:
SWIT_UP@
Access:
Read only
UDC Error Code: N/A
LED:
N/A
UDC Switch Down
Bit 2
The UDC Switch Down bit is on when the
test switch is in the up position.
Hex Value:
0004H
Sug. Var. Name:
SWIT_DN@
Access:
Read only
UDC Error Code: N/A
LED:
N/A
Operating System OK LED
Bit 8
The Operating System OK LED bit shows
the status of the Operating System OK LED
on the UDC module (0 = OFF; 1 = ON).
Hex Value:
0100H
Sug. Var. Name:
N/A
Access:
Read only
UDC Error Code: N/A
LED:
OS OK on UDC
module