Configuring the UDC Module’s Registers

3-19

Drive Control Register (Continued)

100/1100

Enable Notch Filter

Bit 10

The Enable Notch Filter bit is set to
attenuate an undesired frequency in the
speed feedback signal using the speed
loop’s notch filter.

Hex Value:

0400H

Sug. Var. Name:

NTCH_EN@

Access:

Read only

UDC Error Code: N/A
LED:

N/A

UDC Program In Run

Bit 15

The UDC Program In Run bit is a status bit
that indicates that the UDC task is running.
This bit is used by the PMI Regulator to
prevent the minor loop from running if the
UDC task is not running.

Hex Value:

8000H

Sug. Var. Name:

UDC_RUN@

Access:

Read only

UDC Error Code: N/A
LED:

N/A

This bit must NOT be written to by the user. This is a status bit that must only be
written to by the operating system.

I/O Control Register

101/1101

The I/O Control Register contains the bits that control the resolver and drive I/O, resolver strobe operation,
the external loopback test of the fiber-optic ports, and the calculation of Iz for constant power applications.

Stop Interpolation of Field Reference Curve

Bit 0

This bit is set to turn off interpolation of Iz
when using the Constant Power regulators.
Turning off this function permits manual
tuning.

Hex Value:

0001H

Sug. Var. Name:

NO_INTR@

Access:

Read/Write

UDC Error Code: N/A
LED:

EXT FLT

Refer also to the description of register 101/1101, bit 10.

External Fault LED

Bit 2

The External Fault LED bit is set by the
application task to turn on the EXT FLT LED
on the PMI.

Hex Value:

0004H

Sug. Var. Name:

EXT_LED@

Access:

Read/Write

UDC Error Code: N/A
LED:

EXT FLT