Page 54

background image

3-22

SA500 Drive Configuration and Programming

Position Reference Register

106/1106

The value in the Position Reference register is the PMI setpoint in
reference to position feedback. This value must not change by more
than 32767 counts per PMI scan, where 4095 equals one mechanical
revolution of the resolver.

Sug. Var. Name:

POS_STPT%

Units:

Counts

Range:

+32767 to -32768

Access:

Read/Write

Note that +32767 to -32768 is a single count change.

Speed Reference No Ramp Register

107/1107

The value in the Speed Reference No Ramp register is the reference
sent to the PMI for use in the speed loop. It is not used by the speed
loop’s ramp block. This value corresponds to the motor’s
gear-in-speed. The value is limited to not exceed +/-4095.

Sug. Var. Name:

SPD_REF%

Units:

Counts

Range:

+4095 to -4095

Access:

Read/Write

Position Feedback From UDC Register

108/1108

The value in the Position Feedback From UDC register is used by the
PMI position loop when External Variable is selected for Position
Feedback on the parameter entry screen.

Sug. Var. Name:

EXT_POS_FB%

Units:

Counts

Range:

+4095 to -4095

Access:

Read/Write

The change in this value is used to decrement the position error counter. This value must be scaled so that
4095 equals one mechanical revolution of the resolver.

External Reference Flux Weakening Register

109/1109

The External Reference Flux Weakening register is used for speed
feedback when a user-installed device, such as a pulse tachometer,
is used in place of the resolver.

Sug. Var. Name:

EXT_CP_REF%

Units:

RPM

Range:

Application

Access:

Read/Write