Configuring the UDC Module’s Registers

3-37

Interlock Register (Continued)

205/1205

Rising Edge Required

Bit 4

The Rising Edge Required bit is set if a
rising edge is required on any command bit
in register 100/1100.

Hex Value:

0010H

Sug. Var. Name:

IC_RISE@

Access:

Read only

UDC Error Code: N/A
LED:

N/A

This bit will be set if the application task has set the Fault Reset bit (register
100/1100, bit 8) but has not cleared and then re-set any command bits.

More Than One Drive Request

Bit 5

The More Than One Drive Request bit is set
if more than one operating mode is
requested at a time in register 100/1100
(bits 0 and 1).

Hex Value:

0020H

Sug. Var. Name:

IC_MORE@

Access:

Read only

UDC Error Code: N/A
LED:

N/A

MCR Did Not Close

Bit 7

The MCR Did Not Close bit is set if the
optional output contactor did not close when
commanded to do so.

Hex Value:

0080H

Sug. Var. Name:

IC_MCR@

Access:

Read only

UDC Error Code: N/A
LED:

N/A

Speed Feedback Register

206/1206

The Speed Feedback register contains the speed feedback data from
the PMI speed loop.

Sug. Var. Name:

SPD_FB%%

Units:

Counts

Range:

+/-4095

Access:

Read only

Torque Feedback Register

207/1207

The Torque Feedback register contains the torque setpoint feedback
data from the PMI speed loop.

Sug. Var. Name:

TRQ_FB%

Units:

Counts

Range:

+/-4095

Access:

Read only

Position Feedback Register

208/1208

The Position Feedback register contains the position feedback data
from the PMI position loop.

Sug. Var. Name:

POS_FB%

Units:

Counts

Range:

+/-32767

Access:

Read only