Configuring the UDC Module’s Registers

3-27

Drive Status Register (Continued)

200/1200

Positive Position Limit

Bit 4

The PMI sets the Positive Position Limit bit
to indicate that the motor has reached its
positive position limit. When the motor
moves away from the positive position limit,
this bit will be turned off.

Hex Value:

0010H

Sug. Var. Name:

POS_SP@

Access:

Read only

UDC Error Code: N/A
LED:

N/A

Negative Position Limit

Bit 5

The PMI sets the Negative Position Limit bit
to indicate that the motor has reached its
negative position limit. When the motor
moves away from the negative position limit,
this bit will be turned off.

Hex Value:

0020H

Sug. Var. Name:

POS_SM@

Access:

Read only

UDC Error Code: N/A
LED:

N/A

Fault Detected

Bit 8

The PMI Regulator sets the Fault Detected
status bit if any fault is detected. This bit is
reset by bit 8 of register 100/1100.

Hex Value:

0100H

Sug. Var. Name:

FLT@

Access:

Read only

UDC Error Code: N/A
LED:

N/A

See the description of the Drive Fault register (202/1202) for more information.

Warning Detected

Bit 9

The Warning Detected status bit is set if any
warning is detected. This bit is reset by bit 9
of register 100/1100.

Hex Value:

0200H

Sug. Var. Name:

WRN@

Access:

Read only

UDC Error Code: N/A
LED:

N/A

See the description of the Drive Warning register (203/1203) for more information.

Notch Filter Enabled

Bit 10

The PMI Regulator sets this bit to indicate
that the notch filter function is enabled
(register 100/1100, bit 10).

Hex Value:

4000H

Sug. Var. Name:

NTCH_ON@

Access:

Read only

UDC Error Code: N/A
LED:

N/A