Application examples, Application examples -15 – Rockwell Automation FactoryTalk View Machine Edition Users Guide User Manual
Page 191

11
•
Set up security
11-15
•
•
•
• •
3. Specify how many minutes the terminal must be inactive before the automatic logout
occurs.
4. If desired, specify a graphic display to open after the automatic logout.
At run time, when the inactivity period expires, the current user is logged out. Logout
macros assigned to the current user run. The DEFAULT user is logged in. The DEFAULT
user’s login macro runs. The specified graphic display opens (if any).
Application examples
Example: Assign security codes to prevent access to graphic
displays
This example shows how to set up users with access to different graphic displays.
1. Assign security codes to graphic displays as follows:
2. In the Runtime Security editor, assign the security code P to the DEFAULT user.
3. Assign security codes for the displays they can use to the other users:
The users have access to these graphic displays:
MAINTENANCE has access to the first three graphic displays.
OPERATOR has access to the Alarm History and Boiler displays, but not to the
Furnace or Top Secret displays.
To this display
Assign this security code
Alarm History
A
Boiler
B
Furnace
C
Top Secret
D
To this user
Assign these security codes
MAINTENANCE
A, B, C
OPERATOR
A, B
ADMIN
All