beautypg.com

Using the monitor move command – Rockwell Automation 1746-HSRV SLC Servo Control Module User Manual User Manual

Page 134

background image

Publication 1746-6.1.2 - July 2000

Programming the SLC Processor to Run the SLC Servo Module 8-17

The example initiates a speed move:

At 10 position units per timebase

At 100% of the maximum acceleration specified in the
configuration

The speed move occurs if:

The module is out of Estop

The maximum speed configured is more than 10 position units
per minute

Using the Monitor Move Command

The monitor move command allows you to move the axis by external
means with the following error set to 0 and the position monitored
and updated. Monitor move parameters for word 4, bit 3 appear in the
table below.

1

s = Slot number for the SLC Servo Module.

Essentially, this bit places the SLC Servo Module in open loop.

The monitor move ends if any one of the following occurs:

SLC processor cancels the move.

Estop occurs.

SLC processor sends another move from the mutually exclusive
move set.

Planning a Monitor Move

Figure 8.8 shows a typical ladder program block diagram that initiates
a Monitor Move from the SLC processor. Other moves are initiated by
setting appropriate values in the data tables and copying the data to
the appropriate module output words.

Block Command Parameters

Location

1

Format

Possible Values

Default

Monitor Move

O:s.4

BITS

X000 0000 0000 1000

0

More Bit Specifications

O:s.5

BITS

0000 0000 0000 0000

0

IMPORTANT

The Monitor Move cancels a move in progress and
affects the Incremental Position command
component. This command is ignored if the system
is in open loop.