Connect field wiring – Rockwell Automation 1715-OF8I Redundant I/O System User Manual User Manual
Page 79

Rockwell Automation Publication 1715-UM001C-EN-P - March 2014
79
Installation Instructions
Chapter 2
Connect Field Wiring
Connect the field wiring to the screw terminal blocks on the termination
assemblies.
IMPORTANT
The termination assemblies have integral fuses.
IMPORTANT
You must use safety wiring principles if the applicable standards for the system
require you take precautions to avoid external short circuits, because the
internal diagnostics in the 1715 adapter do not detect external short circuits
between channels. These standards include NFPA-72.
ATTENTION: To comply with the CE Low Voltage Directive (LVD), all connections
to this equipment must be powered from a source compliant with safety extra
low voltage (SELV) or protected extra low voltage (PELV).
ATTENTION: To comply with UL restrictions, all connections to this equipment
must be powered from a UL. Listed source compliant with Limited Voltage/
Current per UL 508.