1715-ob8de – Rockwell Automation 1715-OF8I Redundant I/O System User Manual User Manual
Page 308
![background image](/manuals/579361/308/background.png)
308
Rockwell Automation Publication 1715-UM001C-EN-P - March 2014
Appendix G
I/O Tag Definitions
1715-OB8DE
Table 78 - 16-channel Digital Input, Duplex
Tag Name
Data Type
Definition
Fault
DINT, Binary
Module fault bit:
0 when one module is present and reporting valid data, OxFFF_FFFF when no
modules are present, no Logix connection exists, or reported data is invalid.
Data
INT
Input state, one bit per channel for channels 0…15:
0 = Off/de-energized
1 = On, energized
Status
DINT, bit-field
Redundancy and power status:
Bit
Name
Description
0
ModAFault
0 = Good
1 = Fault or module not present
1
ModBFault
0 = Good
1 = Fault or module not present
8
GroupFault
0 = Good
1 = Any channel or module faulted/failed
9
ModAGroupFault
0 = Good
1 = Any channel or module A faulted/failed
10
ModBGroupFault
0 = Good
1 = Any channel or Module B faulted/failed
PtFault
INT
Channel fault status; one bit per channel for channels 0…15:
0 = Normal
1 = Channel is faulted/failed
Open Wire
INT
Open wire diagnostic status; one bit per channel for channels 0…15:
0 = Normal
1 = Indicates open wire detected
ShortCircuit
INT
Short circuit diagnostic status; one bit per channel for channels 0…15:
0 = Normal
1 = Indicates short circuit detected
Indeterminate
INT
Indeterminate diagnostic status; one channel per channel for channels 0…15:
0 = Normal
1 = Indicates indeterminate input voltage detected
Table 79 - 8-channel Digital Output, Simplex, Output
Tag Name
Data Type
Definition
Data
SINT
Output channel commanded data; one bit per channel for channels 0…7:
0 = Off/de-energize
1 = On/energize
AlarmUnlatch
SINT
Unlatch alarm; one bit per channel for channels 0…7; rising edge transition (that is, 0>1)
ResetBlownFuse
SINT
Reset blown electronic fuse, one bit per channel for channels 0…7; rising edge transition (that is, 0>1) resets