beautypg.com

1715 sil 2 periodic task ‘period’ configuration – Rockwell Automation 1715-OF8I Redundant I/O System User Manual User Manual

Page 231

background image

Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

231

Using SIL 2 Add-On Instructions with 1715 Redundant I/O Modules

Chapter 7

Follow these steps to create the SIL 2 periodic task.

1. In the Controller Organizer, right-click the Tasks folder and choose New

Task.

2. Name the Task (SIL 2, for example).
3. Select the Type ‘Periodic’.

1715 SIL 2 Periodic Task ‘Period’ Configuration

The following are recommendations to configure the periodic task ‘period’ for

SIL 2 applications. Set the period to the minimum 1715 SIL 2 module RPI

divided by 2. For example, if the default RPIs are used.

1. Make the period 60/2 = 30 ms.

Table 46 - Module Default RPIs

1715 Module

RPI

Adapter modules

180 ms

Digital modules

60 ms (lowest)

Analog modules

120 ms

IMPORTANT

Note that all 1715 SIL 2 Add-On Instructions have unique timer

presets set to the module RPI / 2, so each Add-On Instruction will

process packets at a rate based on its module RPI. In

Table 46

, the

AENTR will only process a packet at 180/2=90 ms; every third task

period. The analog modules will process a packet at 120/2 = 60

ms; every other task period. The Add-On Instruction obtains the RPI

from the RPI input parameter on the Add-On Instruction, which is

why it is important to enter this value to match the actual module

RPI.

Although the timer preset within the Add-On Instructions equals

RPI/2, the actual rate the Add-On Instructions processes packets is

affected by the periodic task rate and the periodic task scan time.

As these values get lower, the timer resolution improves and

packets are processed closer to the RPI/2 timer preset.

IMPORTANT

Make sure that the SIL 2 task period allows enough time for the SIL 2
task, including the Add-On Instructions, to complete. Adjusting the
period time above the suggested value may be needed if a large

number of 1715 modules is used, as this adds additional Add-On
Instructions. Any increase to the safety task period impacts the safety
reaction time. See

Worst Case Reaction Time Calculations on page 241

.