114
Rockwell Automation Publication 1715-UM001C-EN-P - March 2014
Chapter 2
Installation Instructions
7. Enter the MAC address in the Ethernet Address (MAC): field.
8. Enter the IP address you want to use in the IP address field.
9. Click OK.
10. Click Disable BootP/DHCP to set from dynamic to static.
Step 2: Configure the Module with RSLinx Software
To use RSLinx software to configure the adapter module on the Ethernet
network, follow these steps.
1. Launch RSLinx Classic software.
2. From the Communications menu, choose RSWho.
IMPORTANT
• IP addresses can be recovered, if needed, in the Module Properties tab.
• Note that the second adapter module (rightmost) has a MAC address that is
the first adapter module’s (leftmost) MAC address + 2 in HEX.
00:A0:EC:00:24:8C
00:A0:EC:00:24:8C