I/O Tag Definitions
Appendix G
Data
REAL
Input data
Faults
DINT, bit-field
Channel fault status:
Bit
Name
Description
0
Fault
0 = Good
1 = Circuit fault for this channel
1
ModAFault
0 = Good
1 = This channel on Module A is faulted/
failed
2
ModBFault
0 = Good
1 = This channel on Module B is faulted/
failed
3
Underrange
0 = Good
1 = Underrange detected
4
Overrange
0 = Good
1 = Overrange detected
RollingTimestamp
INT
Timestamp data
Status
DINT, bit-field
Bit
Name
Description
0
ModAFault
0 = Good
1 = Fault or module not present
1
ModBFault
0 = Good
1 = Fault or module not present
8
GroupFault
0 = Good
1 = Any channel on module is faulted/
failed
9
ModAGroupFault
0 = Good
1 = Any channel on Module A is faulted/
failed
10
ModBGroupFault
0 = Good
1 = Any channel on ModuleB is faulted/
failed
Table 83 - 16-channel Analog Input, Duplex, Input