Rockwell Automation 1715-OF8I Redundant I/O System User Manual User Manual
Page 119
Rockwell Automation Publication 1715-UM001C-EN-P - March 2014
119
Installation Instructions
Chapter 2
The following status indicators light depending on which module you are
installing. This is a quick installation reference. For more detailed status indicator
information, see
Appendix A
.
7. Turn the locking screw on the front of the module a 1/4 turn clockwise to
lock, referring to
page 110
• The 1715-IB16D digital input module’s Redundancy Status indicator
shows RED when the screw is locked.
• The 1715-IF16 analog input module’s Redundancy Status indicator
shows RED when the screw is locked.
The module enters its start-up sequence. This takes approximately 3
seconds.
If the module is the first module in a TA group with a running adapter, it
displays the following status indicators. See
Table 15 - Start-up Sequence
1715-IB16D, 1715-OB8DE, 1715-IF16, and 1715-OF8I Modules
Indicator
Status
Module Status
Green
Redundancy Status
Off
Network Status
Red
Channel 0…7, 8…15
Off
Table 16 - First Module in TA Group
1715-IB16D, 1715-OB8DE, and 1715-IF16
Modules
1715-OF8I Module
Indicator
Status
Indicator
Status
Module Status
Green
Module Status
Green
Redundancy Status
Green
Redundancy Status
Red to steady green
Network Status
Amber
Network Status
Amber
Channel 0…7, 8…15
Off
Channel 0…7
Off