1715-ib16d – Rockwell Automation 1715-OF8I Redundant I/O System User Manual User Manual
Page 307
![background image](/manuals/579361/307/background.png)
Rockwell Automation Publication 1715-UM001C-EN-P - March 2014
307
I/O Tag Definitions
Appendix G
1715-IB16D
CIPConnections
DINT
Total number of active CIP connections
CIPLostPackets
DINT
Total of all CIP packets
TCP Connections
DINT
Total of all TCP connections
CUPUtilization
DINT
Echo of Connection Manager object CPU_Utilization attribute
Table 76 - Input
Tag Name
Data Type
Definition
Table 77 - 16-channel Digital Input, Simplex
Tag Name
Data Type
Definition
Fault
DINT, Binary
Module fault bit:
0 when a module is present and reporting valid data, OxFFF_FFFF when no module is
present, no Logix connection exists, or reported data is valid
Data
INT
Input state, one bit per channel for channels 0…15:
0 = Off/de-energized
1 = On, energized
Status
DINT, bit-field
Redundancy and power status:
Bit Name
Description
8 GroupFault
0 = Good
1 = Any channel or module faulted/failed
PtFault
INT
Channel fault status; one bit per channel for channels 0…15:
0 = Normal
1 = Channel is faulted/failed
Open Wire
INT
Open wire diagnostic status; one bit per channel for channels 0…15:
0 = Normal
1 = Indicates open wire detected
ShortCircuit
INT
Short circuit diagnostic status; one bit per channel for channels 0 …15:
0 = Normal
1 = Indicates short circuit detected
Indeterminate
INT
Indeterminate diagnostic status; one channel per channel for channels 0…15:
0 = Normal
1 = Indicates indeterminate input voltage detected