Configure an input module add-on instruction – Rockwell Automation 1715-OF8I Redundant I/O System User Manual User Manual
Page 234
234
Rockwell Automation Publication 1715-UM001C-EN-P - March 2014
Chapter 7
Using SIL 2 Add-On Instructions with 1715 Redundant I/O Modules
Configure an Input Module
Add-On Instruction
Use the following instructions to configure an input module.
Follow these steps to configure an input module Add-On Instruction.
1. From the Instruction toolbar Add-On tab, add the Add-On instruction to
your routine.
2. Create a tag for the Add-On Instruction by using the default data type and
Read/Write External Access.
The tag can be controller- or program-scoped.
3. Create a reset tag by using the default data type and Read/Write External
Access.
IMPORTANT
The 1715-AENTR adapter functions as an input module when using 1715 SIL 2
Add-On Instructions.