Configure an output module add-on instruction – Rockwell Automation 1715-OF8I Redundant I/O System User Manual User Manual
Page 238
238
Rockwell Automation Publication 1715-UM001C-EN-P - March 2014
Chapter 7
Using SIL 2 Add-On Instructions with 1715 Redundant I/O Modules
Configure an Output Module
Add-On Instruction
Follow these steps to configure an output module Add-On Instruction.
1. Add the Add-On Instruction to your routine from the Add-On tab of the
instruction toolbar.
2. Create a tag for the Add-On Instruction by using the default data type and
Read/Write External Access.
The tag can be controller- or program-scoped.
3. Create a reset tag by using the default data type and Read/Write External
Access.
The tag can be controller- or program-scoped.
4. Choose the module configuration tag.
If you have more than one module, be sure to choose the configuration tag
for the appropriate module.
5. Choose the module input tag.
If you have more than one module, be sure to choose the input tag for the
appropriate module.
6. Create a tag for the Reconciled Input Data by using the default data type
and Read/Write External Access.