Digital I/O Operation

Chapter 3

Features Specific to 1715-

OBD8E Digital Output

Modules

The features described in this section are available on all ControlLogix digital

output modules.

Configurable Point-level Output Fault States

Individual outputs can be independently configured to unique fault states, either

On, Off, or Hold in case of a communication failure or Program mode.

Follow these steps to enable a fault state.

1. On the Module Properties dialog box, click the Configuration tab.

2. Choose the Fault mode.
3. Click OK.

Output Data Echo

During normal operation, when a processor sends out an output command to the

ControlLogix system, the output module that is targeted for that command

returns the commanded state of the output to the system. This process verifies

that the module has received the command and tries to execute it.

IMPORTANT

Whenever you inhibit an output module, it enters the Program mode and
all outputs change to the state configured for the Program mode. For

example, if an output module is configured so that the state of the outputs
turn off during Program mode, whenever that module is inhibited, the
outputs turn off.