Rockwell Automation 1715-OF8I Redundant I/O System User Manual User Manual
Page 253
Rockwell Automation Publication 1715-UM001C-EN-P - March 2014
253
Status Indicators
Appendix A
Status indicators for the 1715-AENTR adapter module are shown in this table.
Table 54 Adapter Status Indicators
Indicator
State
Description
Module Status
Steady off
No power - There is no power to the module.
Steady green
Module operational - The module has been configured
without any faults.
Flashing green
Standby - The module has not been configured.
Steady red
Major fault - The module has detected a nonrecoverable
fault.
Flashing green/red
Self-test - The module is performing its power-on self
tests.
Flashing amber
Unlocked - Adapter is unlocked from a previously locked
state.
Redundancy Status
Steady off
No power, unlocked, or no partner - The module is not
locked (via the locking screw), or no partner module is
present.
Steady green
Synchronized - The module is synchronized with the
partner module (redundant operation).
Flashing green
Partner detected, synchronizing - The partner module has
been detected and is synchronizing with its partner
module in preparation for redundant operation.
Steady red
Synchronization fault - The partner module is present, but
unable to synchronize (no redundant operation).
Flashing green/red
Self-test - The module is performing its power-on self
tests.
Flashing amber
Unlocked - Adapter is unlocked from a previously locked
state.
Network Status
Steady off
No power, unlocked, no IP address - The module has no
power, or the module is not locked (via the locking screw),
or no IP address has been assigned or obtained.
Steady green
Connected - The module has at least one established
connection (either to itself or to an
I/O module).
Flashing green
No connections - The module has an IP address, but there
are no established connections (either to itself or an I/O
module).
Flashing red
Connection timeout - One or more of the connections
(either to itself or to an I/O module) has timed out.
Steady red
Duplicate IP - The module has detected that its IP address
is already in use.
Flashing green/red
Self-test - The module is performing its power-on self
tests.
Flashing amber
Unlocked - Adapter is unlocked from a previously locked
state.