1715-IB16D Digital Input Module Diagnostics
Appendix C
Calculate the Voltage for Off/On Conditions for Threshold Values
The following examples calculate the voltage for an ‘off ’ condition with the
switch opened and closed.
Open Switch/Off Condition
With SW1 open, current flows through R1 and R2 (15 + 3.9 k
18.9 k
. We
can calculate the voltage that is present at the input of the input module and by
using a voltage divider circuit, we can calculate the voltage for an ‘off ’ condition.
Figure 75 - Open Switch/Off Condition
Shield
(if used)
Terminal
Blocks
OV
20
Ω
100
Ω
50 mA
4.99k
Ω
Termination
Assembly
+24V dc
R1
R2
45678
User-calculated Voltage
5.1K
SW1
3.9k
15k
45680