G - i/o tag definitions, 1715-aentr adapter module, I/o tag definitions – Rockwell Automation 1715-OF8I Redundant I/O System User Manual User Manual
Page 305: Appendix
Rockwell Automation Publication 1715-UM001C-EN-P - March 2014
305
Appendix
G
I/O Tag Definitions
1715-AENTR Adapter Module
Table 76 - Input
Tag Name
Data Type
Definition
Fault
DINT, Binary
Adapter fault bit: 0 when at least one adapter is present and reporting valid data, OxFFF_FFFF when no adapters
are present, no Logix connection exits, or reported data is invalid.
Status
DINT, bit field
Adapter redundancy and power status:
Bit 0: ModAFault
0 = good
1 = fault or module not present
Bit 1: ModBFault
0 = good
1 = fault or module not present
Bit 8: Power1Fault
0 = good
1 = fault or module not present
Bit 9: Power2Fault
0 = good
1 = fault or module not present
LinkStatus
DINT, bit-field
Adapter module Ethernet port status:
Bit 0: PortA1Connected
0= Inactive
1 = Active
Bit 2: PortA2Connected
0= Inactive
1 = Active
Bit 3: PortB1Connected
0= Inactive
1 = Active
Bit 4: PortB2Connected
0= Inactive
1 = Active
FullDuplex
DINT, bit-field
Adapter module Ethernet port half/full duplex status:
Bit 0: PortA1FullDuplex
0= Inactive
1 = Active
Bit 2: PortA2Duplex
0= Inactive
1 = Active
Bit 3: PortB1Duplex
0= Inactive
1 = Active
Bit 4: PortB2Duplex
0= Inactive
1 = Active