beautypg.com

Rockwell Automation 198x Modular DeviceNet Starter Auxiliary I/O User Manual

Page 94

background image

5-28 Specifications

Publication 198-UM001B-EN-P September 2001

Figure 5.19 198-OW2 Electrical and Application Schematic

Table 5.T 198-OW2 Specifications

Terminal Block

Connection Capacity

Solid wire

0.13…1.5 mm

2

(24…16 AWG)

Flexible wires

0.13…2.5 mm

2

(24…14 AWG)

Flexible wires with ferrules

0.5…2.5 mm

2

(20…14 AWG)

Plastic collar

1.5 mm

2

(16 AWG)

Wire Type

Use 75 C copper wire min.

Tightening Torque

Spring clamp

Electrical

Module Operating Voltage Range

11…25V DC

Module Voltage Rating

24V DC

Module Current Draw

50 mA @ 24V DC

Output Voltage Rating

120V AC

Output Load Current

5 A per output

Switching Device

Relay — B300, AC15

Module Isolation

132V AC working voltage
1500V AC for 1 s

198-OW2

L o r 24V

Ou t A

Ou t A

N or 0V

Ou t B

Ou t B

Load

Load

120V AC

or

24V DC

Typical Wiring