5-46 Specifications

Publication 198-UM001B-EN-P September 2001

Table 5.AB 198-IB2XOB1 Specifications

Terminal Block (5.08 mm Pitch 4-Position)

Connection Capacity

Solid wire

0.13…1.5 mm

2

(24…16 AWG)

Flexible wires

0.13…2.5 mm

2

(24…14 AWG)

Flexible wires with ferrules

0.5…2.5 mm

2

(20…14 AWG)

Plastic collar

1.5 mm

2

(16 AWG)

Wire Type

Use 75 C copper wire min.

Tightening Torque

Spring clamp

Terminal Block (5.08 mm Pitch 2-Position)

Connection Capacity — Flexible wire

0.13…1.5 mm

2

(24…16 AWG)

Wire Type

Use 75 C copper wire min.

Tightening Torque

Insulation displacement

Electrical

Module Operating Voltage Range

11…25V DC

Module Voltage Rating

24V DC

Module Current Draw

14 mA @ 24V DC

Input Voltage Rating

24V DC

Input On-State Voltage Range

10…24V DC

Input On-State Current

3.0 mA @ 10V DC
7.2 mA @ 26V DC

Input Off-State Voltage Range

0…5V DC

Input Off-State Current

<1.5 mA

Input Filter — Software
Selectable (with two I/O modules)

Off to On

1, 2, 4, 8, 16 ms

On to Off

1.3, 2, 4, 8, 16 ms

Input Compatibility

IEC 1+

Output Voltage Rating

24V DC

Output Load Current

2 A per output

Switching Device

Solid-State — N300, DC14

Module Isolation

132V AC working voltage
1500V AC for 1 s