beautypg.com

Rockwell Automation 198x Modular DeviceNet Starter Auxiliary I/O User Manual

Page 145

background image

DeviceNet Information A-5

Publication 198-UM001B-EN-P September 2001

The following instance attributes are supported:

The following common services are implemented for the Identity Object:

Table A.3 Identity Object Instance Attributes

Attribute

ID

Access

Rule

Name

Data Type

Value

1

Get

Vendor ID

UINT

1

2

Get

Device Type

UINT

12 Communications Adapter

3

Get

Product Code

UINT

Cat. No. 198-DN = 67
Cat. No. 198-DNG = 98

4

Get

Revision

Major Revision
Minor Revision

Structure of:

USINT
USINT

3
1

5

Get

Status

WORD

Bit 0-0 = Not owned
Bit 0-1 = Owned by Master
Bit 2-0 = Out-of-the-Box
Configuration (with the exception
of the MAC ID)
Bit 2-1 = Configured
Bit 8 = Minor Recoverable Fault
Bit 9 = Minor Unrecoverable Fault
Bit 10 = Major Recoverable Fault
Bit 11 = Major Recoverable Fault

6

Get

Serial Number

UDINT

Unique Number

7

Get

Product Name
String Length
ASCII String

SHORT_

STRING

11 Modular-DSA

9

Get

Configuration
Consistency Value

UINT

CRC of configuration data stored in
EEprom

Table A.4 Identity Object Common Services

Service Code

Implemented for:

Service Name

Class

Instance

0x0E

Yes

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single

0x05

No

Yes

Reset (DeviceNet only)