Chapter 2 - installation, Chapter objectives, Storage and operation – Rockwell Automation 198x Modular DeviceNet Starter Auxiliary I/O User Manual
Page 14: Chapter 2 — installation, Chapter objectives -1 storage and operation -1, Installation, Chapter

Publication 198-UM001B-EN-P September 2001
Chapter
2
Installation
Chapter Objectives
This chapter contains information about:
• Device storage and operating environment
• Mounting
• Connecting and wiring
Storage and Operation
To prolong the product life, take the following precautions:
• Store within an ambient temperature range of –40…+85°C (–40…+185°F).
• Store within a relative humidity range of 0…95%, non-condensing.
• Avoid storing or operating the device where it could be exposed to a corrosive
atmosphere.
• Protect from moisture and direct sunlight.
• Operate at an ambient temperature range of –25…+60°C (–4…+140°F). The
Modular-DSA I/O System enclosure is suitable for an ambient of –25…+40
°C.
Modular-DSA I/O System is suitable for use in an industrial environment when installed in
accordance with these instructions. Specifically, this equipment is intended for use in a clean,
dry environment (Pollution Degree 2
➊
)
➋
.
➊ Pollution Degree 2 is an environmentally where, normally, only non-conductive pollution occurs except
occasionally a temporary conductivity caused by condensation shall be expected.
➋ Pollution Degree 2 is an International Electrotechnical Commission (IEC) designations.