5-6 Specifications

Publication 198-UM001B-EN-P September 2001

198-DNP (Mini DIN Pass-Through)

The 198-DNP is designed to provide a connection from the outside of an enclosure to
internally-mounted DeviceNet products such as a DIN Rail-Mounted Modular-DSA I/O
System.

Figure 5.3 198-DNP Electrical and Application Schematic

Table 5.D M12 Mini DeviceNet Connector

Thread M12*1

Voltage

24V

Current

5 A

Mounting Hole

16 mm (5/8 in.)

Torque M12 Connector

1.4 Nm (12 in.-lb)

198-DNP

24V, 8A Max

CAN H (White) (4)
24V+ Red (5)

CAN L (Blue) (2)

24V- (Black) (1)

Shield (Bare) (3)

Wiring Diagram

Typical Installation