I/o error mode, I/o idle mode, Object definitions – Rockwell Automation 198x Modular DeviceNet Starter Auxiliary I/O User Manual

Page 144: Devicenet objects, Identity object— class id (01hex), Identity object — class id (01hex)

background image

A-4 DeviceNet Information

Publication 198-UM001B-EN-P September 2001

I/O Error Mode

In I/O Error Mode, the status of all the outputs will be set to values and states as defined in
the fault action and value selections of the discrete output object. The I/O Status LED may
be solid red. This condition can be caused by an I/O Bus fault, such as a module being
removed. The I/O Status LED could also be flashing red. This condition can be caused by a
DeviceNet connection timing out. For full definition of LED conditions refer to the I/O
Status LED
in Chapter 5
.

I/O Idle Mode

In I/O Idle Mode, the status of all the outputs will be set to values and states as defined in the
idle action and value selections of the discrete output object. The I/O Status LED will be
flashing green. For full definition of LED conditions. refer to the I/O Status LED in
Chapter 5.

Object Definitions

DeviceNet Objects

The following object classes are supported.

Identity Object — Class ID (01hex)

The following class attributes are supported for the Identity Object:

Table A.1 Object Definitions

Class

Object

Class

Object

1

Identity

08hex

Discrete Input Point

2

Message Router

09hex

Discrete Output Point

3

DeviceNet

0Ehex

Presence Sensing

4

Assembly

2Bhex

Acknowledge Handler

5

Connection

B4hex

DeviceNet Interface Object

Table A.2 Identity Object Class Attributes

Attribute ID

Access Rule

Name

Data Type

Value

1

Get

Revision

UINT

1