Detecting and eliminating emc interferences, Electrical installation – Lenze i700 Manual User Manual

Page 98

background image

Electrical installation

Installation according to EMC (installation of a CE−typical drive system)
Detecting and eliminating EMC interferences

6

l

98

EDS700ACBA EN 4.0

6.3.6

Detecting and eliminating EMC interferences

Fault

Cause

Remedy

Interferences of analog
setpoints of your own or
other devices and
measuring systems

Unshielded motor cable

Use shielded motor cable

Shield contact is not extensive enough

Carry out optimal shielding as specified

Shield of the motor cable is interrupted
by terminal strips, switched, etc.

l

Separate components from other
component part with a minimum
distance of 100 mm

l

Use motor choke/motor filter

Install additional unshielded cables
inside the motor cable (e.g. for motor
temperature monitoring)

Install and shield additional cables
separately

Too long and unshielded cable ends of
the motor cable

Shorten unshielded cable ends to
maximally 40 mm

Conducted interference
level is exceeded on the
supply side

Terminal strips for the motor cable are
directly located next to the mains
terminals

Spatially separate the terminal strips for
the motor cable from main terminals
and other control terminals with a
minimum distance of 100 mm

Mounting plate varnished

Optimise PE connection:

l

Remove varnish

l

Use zinc−coated mounting plate

HF short circuit

Check cable routing