Page 113: Dc−supply power, Dc−bus operation

background image

DC−bus operation

Rated data

General data

7

l

113

EDS700ACBA EN 4.0

7.4

Rated data

7.4.1

General data

The total current of the nominal input currents I

DC

to be provided by the power supply

module must be determined. If required, the DC cables must be dimensioned in
accordance with the total current.

Additional data

Input current

DC−bus capacity

Charging resistor

I

DC

at I

ar

[A]

[

mF]

[

W]

E70ACMSx0054xx1xxx

5.0

165

100

E70ACMSx0104xx1xxx

9.3

165

100

E70ACMSx0204xx1xxx

18.4

330

100

E70ACMSx0324xx1xxx

29.8

720

34

E70ACMSx0484xx1xxx

44.6

1080

34

E70ACMSx0644xx1xxx

59.5

1080

34

E70ACMSx0054xx2xxx

9.3

165

100

E70ACMSx0104xx2xxx

18.4

330

100

E70ACMSx0204xx2xxx

37.3

720

34

E70ACMSx0324xx2xxx

59.5

1080

34

Tab. 7−1

DCbus = DC bus

7.4.2

DC−supply power

The parameters relevant for the selection of a supply unit with a suitable supply power
(even in the overload range) are listed in the below table:

U

LN

Rated AC voltage

Cycle 1

Cycle for the second−range

Cycle 2

Cycle for the minute−range

P

DC 100%

Permanent power of DC−voltage level

P

ol

Power supply during overload time

t

ol

Overload time

P

re

Power supply during unloading time

t

re

Relief time

Any other cycles are calculated with the following formula:

(P

ol

@ t

ol

) ) (P

re

@ t

re

)

t

ol

) t

re

v P

DC 100%

Cycles other than the above cycles must not exceed the specified power and time values,
i.e. the values must be used as maximum values.

The values depend on the rated AC voltage U

Lr

.