Rated data, General data, Dc-supply power – Lenze i700 Manual User Manual
Page 113: Dc−supply power, Dc−bus operation
DC−bus operation
Rated data
General data
l
113
EDS700ACBA EN 4.0
7.4
Rated data
7.4.1
General data
The total current of the nominal input currents I
DC
to be provided by the power supply
module must be determined. If required, the DC cables must be dimensioned in
accordance with the total current.
Additional data
Input current
DC−bus capacity
Charging resistor
I
DC
at I
ar
[A]
[
mF]
[
W]
E70ACMSx0054xx1xxx
5.0
165
100
E70ACMSx0104xx1xxx
9.3
165
100
E70ACMSx0204xx1xxx
18.4
330
100
E70ACMSx0324xx1xxx
29.8
720
34
E70ACMSx0484xx1xxx
44.6
1080
34
E70ACMSx0644xx1xxx
59.5
1080
34
E70ACMSx0054xx2xxx
9.3
165
100
E70ACMSx0104xx2xxx
18.4
330
100
E70ACMSx0204xx2xxx
37.3
720
34
E70ACMSx0324xx2xxx
59.5
1080
34
Tab. 7−1
DCbus = DC bus
7.4.2
DC−supply power
The parameters relevant for the selection of a supply unit with a suitable supply power
(even in the overload range) are listed in the below table:
U
LN
Rated AC voltage
Cycle 1
Cycle for the second−range
Cycle 2
Cycle for the minute−range
P
DC 100%
Permanent power of DC−voltage level
P
ol
Power supply during overload time
t
ol
Overload time
P
re
Power supply during unloading time
t
re
Relief time
Any other cycles are calculated with the following formula:
(P
ol
@ t
ol
) ) (P
re
@ t
re
)
t
ol
) t
re
v P
DC 100%
Cycles other than the above cycles must not exceed the specified power and time values,
i.e. the values must be used as maximum values.
The values depend on the rated AC voltage U
Lr
.