Technical data, Terminal description supply modules, Digital inputs, digital outputs – Lenze i700 Manual User Manual
Page 45
Technical data
Terminal description
Supply modules
l
45
EDS700ACBA EN 4.0
Digital inputs, digital outputs
X20
Labelling
Description
DI1
External brake chopper control
X20.1: digital inputs
DI2
TRIP reset
DI3
SLAVE activation
DO1
Brake chopper status output
X20.2: digital outputs
Diagnostic information:
^ 124
DO2
Error message
GD
Reference potential GND
For DI1, DI2, DI3, DO1, DO2
i700PX020
Terminal data
Conductor cross−section
Tightening torque
!
[mm
2
]
[AWG]
[Nm]
[lb−in]
flexible
0.2 ... 2.5
24 ... 12
−
−
3.5 x 0.6
X20
Electrical data
Rated voltage
24 V
in accordance with
IEC 61131−2
Voltage range
19.2 ... 28.8 V
Residual ripple
Max.
± 5 %
DI1
DI2
DI3
Current consumption
Max. 8 mA
Polarity reversal
protection
When polarity is reversed: no function and no
destruction.
DO1
DO2
Current
Max. 50 mA
GD
Reference potential
0 V
X20.2
DO1
DO2
GD
X20.1
DI1
DI2
DI3
DC 24 V
(+19.2...+28.8 V)
i700S010
Fig. 2
Wiring of X20
X20
Connection of digital inputs and outputs at the power supply module
.1
Connector on the left−hand side
.2
Connector on the right−hand side
DIx
Digital input
DOx
Digital output (e.g. for controlling relays)
GD
Reference potential GND