beautypg.com

Technical data, Terminal description supply modules, Digital inputs, digital outputs – Lenze i700 Manual User Manual

Page 45

background image

Technical data

Terminal description

Supply modules

4

l

45

EDS700ACBA EN 4.0

Digital inputs, digital outputs

X20

Labelling

Description

DI1

External brake chopper control

X20.1: digital inputs

DI2

TRIP reset

DI3

SLAVE activation

DO1

Brake chopper status output

X20.2: digital outputs
Diagnostic information:

^ 124

DO2

Error message

GD

Reference potential GND

For DI1, DI2, DI3, DO1, DO2

i700PX020

Terminal data

Conductor cross−section

Tightening torque

!

[mm

2

]

[AWG]

[Nm]

[lb−in]

flexible

0.2 ... 2.5

24 ... 12

3.5 x 0.6

X20

Electrical data

Rated voltage

24 V

in accordance with
IEC 61131−2

Voltage range

19.2 ... 28.8 V

Residual ripple

Max.

± 5 %

DI1
DI2
DI3

Current consumption

Max. 8 mA

Polarity reversal
protection

When polarity is reversed: no function and no
destruction.

DO1
DO2

Current

Max. 50 mA

GD

Reference potential

0 V

X20.2

DO1

DO2

GD

X20.1

DI1

DI2

DI3

DC 24 V

(+19.2...+28.8 V)

i700S010

Fig. 2

Wiring of X20

X20

Connection of digital inputs and outputs at the power supply module

.1

Connector on the left−hand side

.2

Connector on the right−hand side

DIx

Digital input

DOx

Digital output (e.g. for controlling relays)

GD

Reference potential GND