beautypg.com

Installation in the control cabinet, Electrical installation – Lenze i700 Manual User Manual

Page 95

background image

Electrical installation

Installation according to EMC (installation of a CE−typical drive system)

Installation in the control cabinet

6

l

95

EDS700ACBA EN 4.0

6.3.4

Installation in the control cabinet

Mounting plate requirements

ƒ

Only use mounting plates with conductive surfaces (zinc−coated or V2A−steel).

ƒ

Painted mounting plates are not suitable even if the paint is removed from the
contact surfaces.

ƒ

If several mounting plates are used, ensure a large−surface connection between the
mounting plates (e.g. by using earthing strips).

Mounting of the components

The trouble−free operation of power supply modules with an external brake resistor is only
ensured if an axis module is installed in the immediate vicinity. Preferably by end−to−end
mounting and use of the DC busbar system (X101/X102).

ƒ

Connect the controller and RFI filter to the grounded mounting plate with a surface
as large as possible.

ƒ

No DIN rail mounting!

Optimum cable routing

ƒ

The motor cable is optimally installed if
– it is separated from mains cables and control cables,
– it crosses mains cables and control cables at right angles.

ƒ

Always install cables close to the mounting plate (reference potential), as freely
suspended cables act like aerials.

ƒ

Lead the cables to the terminals in a straight line (avoid tangles of cables).

ƒ

Use separated cable channels for motor cables and control cables. Do not mix up
different cable types in one cable channel.

ƒ

Minimise coupling capacities and coupling inductances by avoiding unnecessary
cable lengths and reserve loops.

ƒ

Short−circuit unused cores to the reference potential.

ƒ

Install the positive and negative wires for DC 24 V close to each other over the entire
length to avoid loops.

Earth connections

ƒ

Connect all components (drive controllers, chokes, filters) to a central earthing point
(PE rail).

ƒ

Set up a star−shape earthing system.

ƒ

Comply with the corresponding minimum cable cross−sections.