Electrical installation

Safety instructions for the installation according to UL

6

l

87

EDS700ACBA EN 4.0

6.2

Safety instructions for the installation according to UL

Original − English

J

Warnings!

ƒ

Use 60/75 °C copper wire only, except for control circuits.

ƒ

Suitable for use in a surrounding air temperature of 40 °C, and additionally
55 °C when the derating rules are followed.

ƒ

Voltage of the fuses must at least be suitable for the input voltage of the
drive.

ƒ

The opening of branch circuit protective device may be an indication that a
fault has been interrupted. To reduce the risk of fire or electric shock,
current−carrying parts and other components of the controller should be
examined and replaced if damaged.

ƒ

For E70ACPS0304x AC/DC power supply module only:
– Suitable for use on a circuit capable of delivering not more than 100 k rms

symmetrical amperes, 480 V max,

– when protected by class J, T or G fuses or protected by a circuit breaker

having an interrupting rating not less than 100 k rms symmetrical
amperes, 480 V.

– Use fuses or circuit breakers only.

ƒ

For E70ACPS0604x AC/DC power supply module only:
– Suitable for use on a circuit capable of delivering not more than 100 k rms

symmetrical amperes, 480 V max,

– when protected by class J, T or G fuses.
– Use fuses only.

ƒ

E70ACMSxxxx4x... DC/AC inverter units:
– The integral solid state protection does not provide branch circuit

protection. Branch circuit protection has to be provided externally in
accordance with the National Electrical Code and any additional codes.

ƒ

E70ACMSxxxx4x... DC/AC inverter units, connected to an external
DC power supply:
– Overload protection: 125 % of rated FLA