Axis modules, Electrical installation – Lenze i700 Manual User Manual

Page 105

background image

Electrical installation

Axis modules

6

l

105

EDS700ACBA EN 4.0

6.7

Axis modules

For all connections, the chapter "Technical data, connection description" provides the
following detailed information:

ƒ

Rated data

ƒ

Assignment

ƒ

Circuit diagram for the electrical connection

Interconnections required for the axis module:

Connections and elements

Info

X1

Safe input STO

^ 50

X2

Touch probe

^ 51

X3

External 24−V supply

^ 52

X4

EtherCAT IN

^ 53

X5

EtherCAT OUT

Servo control feedback (alternative)

X7 − resolver

^ 55

X8 − encoder

^ 57

X101

DC−bus voltage +UG

^ 59

X102

DC−bus voltage −UG

X108

Motor A

^ 62

X107

Motor B

X105

24−V supply of motor holding brake(s)

^ 60

X106

Motor holding brake

^ 61

+

PE conductor

^ 101

"

Shield connection (functional earth)

^ 101

)

Note!

If integrated safety is not to be used for an axis, the safe inputs SIA and SIB of
the axis must be fixedly assigned with "HIGH" potential (24 V).
The wiring should not give the impression of connected safety sensors, or
should be provided with adequate labelling.

)

Note!

Earth the motor separately (see basic circuit diagram).
Earthing only via the motor cable does not provide sufficient protection
because the mains fuse does not protect the motor cable.

ƒ

In the drive system, the supply feeder is usually designed more strongly
than the motor cables. Therefore, in the event of an error (e.g. earth fault),
the mains fuse is able to protect the motor cable and thus also the PE in the
motor cable.