Electrical installation

Installation according to EMC (installation of a CE−typical drive system)
Motor cable

6

l

94

EDS700ACBA EN 4.0

6.3.3

Motor cable

ƒ

Only use shielded motor cables with braids made of tinned or nickel−plated copper.
Shields made of steel braids are not suitable.
– The overlap rate of the braid must be at least 70 % with an overlap angle of 90 °.

ƒ

The cables used must correspond to the requirements at the location (e.g.
EN 60204−1).

ƒ

Connect the shield with a large surface and fix it with metal cable binders or a
conductive clamp.

ƒ

Connect the shield directly to the corresponding device shield sheet.
– If required, additionally connect the shield to the conductive and earthed

mounting plate in the control cabinet.

ƒ

The motor cable is optimally installed if
– it is separated from mains cables and control cables,
– it only crosses mains cables and control cables at right angles,
– it is not interrupted.

ƒ

If the motor cable must be opened all the same (e.g. due to chokes, contactors, or
terminals):
– The unshielded cable ends may not be longer than 100 mm (depending on the

cable cross−section).

– Install chokes, contactors, terminals etc. spatially separated from other

components (with a min. distance of 100 mm).

– Install the shield of the motor cable directly before and behind the point of

separation to the mounting plate with a large surface.

ƒ

Connect the shield with a large surface to PE in the terminal box of the motor at the
motor housing.
– Metal EMC cable glands at the motor terminal box ensure a large surface

connection of the shield with the motor housing.

Motor supply cable

Cable gland

Motor supply cable

max. 500mm

Large-surface
contact of
cable shield

Braid

Heat-shrinkable tube

Cable gland acc. to EMC with
high degree of protection

Cable gland

8200EMV023

8200EMV024

Fig. 6−2

Shielding of the motor cable