beautypg.com

Technical data – Lenze i700 Manual User Manual

Page 47

background image

Technical data

Terminal description

Supply modules

4

l

47

EDS700ACBA EN 4.0

Connection to the DC bus (+U

G

, −U

G

)

X101/X102

Labelling

Description

UG+

DC−bus voltage UG+

UG−

DC−bus voltage UG−

Open the protection cover only if the device is deenergised!
To open the protection cover, press the lock between the clips of the
cover down using a screwdriver and swivel the protection cover
away from the device at the same time.

i700PX1012

Terminal data

Conductor cross−section

Tightening torque

!

[mm

2

]

[AWG]

[Nm]

[lb−in]

Swivel hook

5.0

44.3

PH 3

X101
X102

Electrical data

UG+
UG−

Rated voltage

565/675 V

Current

Up to 40 °C: 100 A
40 ... 55 °C: −2.5 %/K

Polarity reversal
protection

For internal connection: not relevant