Safety engineering

Technical data

10

l

134

EDS700ACBA EN 4.0

Safety−related parameters acc.to IEC 61508−1 to −7 and IEC 62061

Specification

Value

Comment

Safety Integrity Level

SIL 3

PFH [1/h]

7.79 E−10 0.78 % of SIL 3

PFD

6.82 E−5

6.8 % of SIL 3 after T = 20 years

Proof test interval

20 years

Mission time

Safety−related parameters acc. to EN ISO 13849−1

Specification

Value

Comment

Performance Level

e

Category

4

MTTF

d

high

71285 years

Diagnostic coverage DC

high

99 %

Note on safety−related parameters

Source of failure rates

SN 29500

As far as values from the
component manufacturers
were not available

Average max. ambient temperature

40 °C

General assumption that 50 % of the failures of
a component are hazardous failures

l

d

= 0.5

l, MTTFd = 2 MTTF

As far as other information was