Electrical installation

Installation according to EMC (installation of a CE−typical drive system)

Mains connection, DC supply

6

l

93

EDS700ACBA EN 4.0

6.3.2

Mains connection, DC supply

ƒ

Power supply modules, mains chokes or mains filters may be connected to the
mains via unshielded single cores or unshielded cables.

ƒ

Cables between mains filters/RFI filters and power supply modules:
– Install twisted and with sufficient distance to adjacent cables.
– If cables are routed together in a cable duct or if longer cable lengths are used, we

recommend the use of shielded cables, e.g. between two control cabinets.

ƒ

The integrated DC busbars (X101/102) do not require EMC measures.

ƒ

Installation of cables for DC supply:
– Up to a length of 300 mm, twisted unshielded cables can be used, e.g. between an

upper and a lower installation row.

– From a length of 300 mm onwards, we recommend the use of shielded cables, e.g.

between two control cabinets.

ƒ

The cable cross−section must be dimensioned for the assigned fusing (observe
national and regional regulations).