Technical data, Rated data supply modules – Lenze i700 Manual User Manual
Page 35

Technical data
Rated data
Supply modules
l
35
EDS700ACBA EN 4.0
Fuses and cable cross−sections
Operation with external mains choke/mains filter
Type
Installation according to EN 60204−1
1)
Installation according to UL
2)
FI
3)
L1, L2, L3 − Laying system
L1, L2, L3
B2
C
F
[A]
[A]
[mm
2
]
[mm
2
]
[mm
2
]
[A]
[A]
[AWG]
[mA]
E70ACPSx0304x
C40
40
10
6
−
40
40
8
³ 300
E70ACPSx0604x
C63
63
16
10
−
−
60
6
³ 300
1)
The data are recommendations. Other designs/laying systems are possible (e.g. in accordance with VDE 0298−4). The
cable cross−sections apply under the following conditions: use of PVC−insulated copper cables, conductor
temperature < 70 °C, ambient temperature < 45°C, no cable or core bundling, three loaded cores.
2)
Only use UL−approved cables, fuses, and fuse holders.
UL fuse: voltage
³ 500 V, tripping characteristic "J", "T", or "G". The cable cross−sections apply under the following
conditions: conductor temperature < 75 °C, ambient temperature < 45°C.
3)
Universal−current sensitive earth−leakage circuit breaker, short−time delayed, type B
In the case of cable lengths > 50m, depending on the cable type and the switching frequency, the circuit−breaker
may respond.
Circuit breaker
Fuse of gG/gL utilisation category or semiconductor fuses of gRL utilisation category
Fuse
Observe national and regional regulations