Mechanical installation – Lenze i700 Manual User Manual

Page 79

background image

Mechanical installation

Notes on mounting the device version in push−through design

Assembly in push−through technique (thermal separation)

5

l

79

EDS700ACBA EN 4.0

Cooling by forced ventilation

Required:

ƒ

Forced ventilation by one or several fans.

ƒ

Air speed: 2.5 m/s at the MP measuring point
– For fan dimensioning: Corresponds to a volume flow of 0.5 m

3

/min (17.6 CFM) per

50 mm device installation width.

Permissible:

ƒ

Operation with continuous output current I

a

= I

rated

.

ƒ

Operation according to rated data.

ƒ

Switching frequencies f

ch

: 4 kHz, 8 kHz and 16 kHz

Cooling by means of natural convection

Required:

ƒ

Unhindered ventilation by means of natural convection (no fan required).

ƒ

Ambient temperature: T

amb

< 40 °C

Permissible:

ƒ

Operation with reduced output current I

a

according to Tab. 5−2.

ƒ

Switching frequencies f

ch

= 4 kHz and 8 kHz

Type

I

a

[A]

E70ACPxD0304x

25

E70ACPxD0604x

50

I

a

[A]

Type

4 kHz

8 kHz

16 kHz

E70ACMxD0054xx1ETx

2.5

2.5

E70ACMxD0104xx1ETx

5.0

5.0

E70ACMxD0204xx1ETx

6.0

6.0

E70ACMxD0054xx2ETx

2 x 2.5

2 x 2.5

E70ACMxD0104xx2ETx

S 5.0

S 5.0

E70ACMxD0324xx1ETx

12.0

9.6

E70ACMxD0484xx1ETx

14.0

11.2

E70ACMxD0644xx1ETx

16.0

12.8

E70ACMxD0204xx2ETx

S 10.0

S 10.0

E70ACMxD0324xx2ETx

S 12.0

S 9.6

Tab. 5−2

Permissible currents I

a

in case of natural convection

S Sum of the output currents axis A and axis B