Storage System Hardware Components

80

Enterprise Virtual Array 3000 User Guide

Table 11: Nonoperational I/O Module LED Descriptions and Status Displays

Top LED

Power LED

Bottom LED

Descriptions

On

On

Off

Top Port—FC-AL signal detected.

Power—Present (After one minute the power LED

will be On constantly).

Bottom Port—No FC-AL signal detected.

Check transceiver and fiber cable connections.

Note:

This status is also displayed when connected

to a FC Loop switch.

Off

On

On

Top Port—No FC-AL signal detected.

Check transceiver and fiber cable connections.

Power—Present.

Bottom Port—FC-AL signal detected.

Flashing

On

On

Top Port—EMU detected possible transceiver

problem.

Check transceiver and fiber cable connections.

Power—Present.

Bottom Port—FC-AL signal detected.

On

On

Flashing

Top Port—FC-AL signal detected.
Power—Present.
Bottom Port—EMU detected possible transceiver

problem.

Check transceiver and fiber cable connections.

Note:

The EMU will not blink the bottom LED on its

own. It will only blink in response to a locate

command. You can blink each of the lights

independently for a locate and, if so, they may not

be in unison.

Off

Off

Off

No I/O module power.

I/O module is nonoperational.

Check power supplies. If power supplies are

operational, replace I/O module.