Regulatory Notices and Specifications

152

Enterprise Virtual Array 3000 User Guide

Caution:

The AC power distribution within a rack ensures a balanced load to

each PDU and reduces the possibility of an overload condition. Changing the

cabling to or from a PDM could cause an overload condition.

Table 31

defines the AC input current and wattage to the power supplies.

Table 30: Enterprise Storage System AC Input Line Voltages

Specification

Minimal

Nominal

Maximum

60 Hz Service
AC Line Frequency

57 Hz

60 Hz

63 Hz

AC Line Voltage–Japan

180 VAC

202 VAC

220 VAC

AC Line Voltage–North America

180 VAC

208 VAC

220 VAC

AC Line Voltage–Europe

208 VAC

240 VAC

254 VAC

50 Hz Service
AC Line Frequency

47 Hz

50 Hz

53 Hz

AC Line Voltage–Japan

180 VAC

202 VAC

220 VAC

AC Line Voltage–North America

190 VAC

220 VAC

235 VAC

AC Line Voltage–North America

200 VAC

230 VAC

244 VAC

AC Line Voltage–Europe

208 VAC

240 VAC

254 VAC

Table 31: AC Input Current and Wattage

Nominal

Maximum

Input Voltage

Amps

Watts

Amps

Watts

60-Hz Input
100 VAC–JBOD

4.35

436

6.41

641

208 VAC–North America

2.03

419

2.94

609

50-Hz Input
120 VAC–JBOD

3.59

419

5.27

633

220 VAC–North America

1.92

418

2.78

608

230 VAC–North America

1.92

418

2.78

608

240 VAC–Europe

1.76

416

2.55

607