En.02 critical condition-high temperature, En.03 noncritical condition-low temperature – HP 3000 Enterprise Virtual Array User Manual

Page 173

background image

EMU Generated Condition Reports

173

Enterprise Virtual Array 3000 User Guide

4. Ensure that both blowers are operating properly (the LEDs are on) and neither

blower is operating at high speed.

5. Verify that the ambient temperature range is +10 °C to +35 °C

(+50 °F to +95 °F). Adjust as necessary.

6. Observe the EMU to ensure the error is corrected.

7. If unable to correct the problem, contact your HP authorized service

representative.

0.4.en.02 CRITICAL Condition

High Temperature

This condition report indicates that an element temperature is above the high
temperature CRITICAL threshold. Continued operation under these conditions
may result in element failure and may reduce an element MTBF. This condition
report remains active until the problem is corrected.

Complete the following procedure to correct this problem.

1. Record all six characters of the condition report.

2. Ensure that all elements are properly installed to maintain proper air flow.

3. Ensure that nothing is obstructing the air flow at either the front of the

enclosure or the rear of the blower.

4. Ensure that both blowers are operating properly (the LEDs are on) and neither

blower is operating at high speed.

5. Verify that the ambient temperature range is +10 °C to +35 °C

(+50 °F to +95 °F). Adjust as necessary.

6. Observe the EMU to ensure the error is corrected.

7. If unable to correct the problem, contact your HP authorized service

representative.

0.4.en.03 NONCRITICAL Condition

Low Temperature

This condition report indicates that an element temperature is approaching, but
has not reached, the low temperature CRITICAL threshold. Continued operation
under these conditions may result in a CRITICAL condition. This condition report
remains active until the problem is corrected.

Complete the following procedure to correct this problem.

1. Record all six characters of the condition report.

2. Verify that the ambient temperature range is +10 °C to +35 °C

(+50 °F to +95 °F). Adjust as necessary.