Power supply conditions, 65 power supply element numbering, Figure 65 – HP 3000 Enterprise Virtual Array User Manual

Page 167

background image

EMU Generated Condition Reports

167

Enterprise Virtual Array 3000 User Guide

7. Observe the EMU to ensure the error is corrected.

8. If unable to correct the problem, contact your HP authorized service

representative.

Power Supply Conditions

The format of a power supply condition report is 0.2.en.ec, where:

0.2. is the power supply element type number

en. is the two-character power supply element number

ec is the error code

Figure 65

shows the location of power supply 1 1, and power supply 2 2.

Figure 65: Power supply element numbering

The following sections define the power supply condition reports.

0.2.en.01 NONCRITICAL Condition

Power Supply AC Input Missing

The loss of the AC input to a power supply makes the remaining supply a single
point of failure.

This condition report remains active until AC power is applied to the power
supply.

Complete the following procedure to correct this problem:

1. Record all six characters of the condition report.

2. Ensure that there is AC power to the rack PDU, and from the PDU to the

PDMs and that the PDU and PDM circuit breakers are not reset.
If there is no AC power to the PDU, contact building facilities management.
Verify that the power supply AC power cord is properly connected.

CXO7952A

2

1