Power supply conditions, 65 power supply element numbering, Figure 65 – HP 3000 Enterprise Virtual Array User Manual
Page 167
EMU Generated Condition Reports
167
Enterprise Virtual Array 3000 User Guide
7. Observe the EMU to ensure the error is corrected.
8. If unable to correct the problem, contact your HP authorized service
representative.
Power Supply Conditions
The format of a power supply condition report is 0.2.en.ec, where:
■
0.2. is the power supply element type number
■
en. is the two-character power supply element number
■
ec is the error code
shows the location of power supply 1 1, and power supply 2 2.
Figure 65: Power supply element numbering
The following sections define the power supply condition reports.
0.2.en.01 NONCRITICAL Condition
—
Power Supply AC Input Missing
The loss of the AC input to a power supply makes the remaining supply a single
point of failure.
This condition report remains active until AC power is applied to the power
supply.
Complete the following procedure to correct this problem:
1. Record all six characters of the condition report.
2. Ensure that there is AC power to the rack PDU, and from the PDU to the
PDMs and that the PDU and PDM circuit breakers are not reset.
If there is no AC power to the PDU, contact building facilities management.
Verify that the power supply AC power cord is properly connected.