En.02 unrecoverable condition-power supply missing – HP 3000 Enterprise Virtual Array User Manual
Page 168

EMU Generated Condition Reports
168
Enterprise Virtual Array 3000 User Guide
3. If AC is present, and the rack power distribution circuitry is functioning
properly, the power supply LED should be on.
4. Observe the EMU to ensure the error is corrected.
5. If unable to correct the problem, contact your HP authorized service
representative.
0.2.en.02 UNRECOVERABLE Condition
—
Power Supply Missing
This condition report indicates a power supply is not installed or installed
incorrectly. Both of these conditions affect air flow within the enclosure and can
cause an overtemperature condition. Enclosure shutdown is imminent.
The operational power supply will automatically shut down after 7 minutes,
thereby disabling the enclosure. This condition report remains active until either
the problem is corrected, or the operational power supply shuts down, whichever
occurs first.
To correct this problem, record all six characters of the condition report, then
contact your HP authorized service representative.
Caution:
Removing power from an enclosure may cause the loss or corruption
of data. To avoid this condition, shut down the system using Command View
EVA.
0.2.en.03 CRITICAL Condition
—
Power Supply Load Unbalanced
This condition report indicates that a component within a power supply may have
failed. This can make the remaining power supply a single point of failure.
This condition report remains active until corrected.
Complete the following procedure to correct this problem:
1. Record all six characters of the condition report.
2. Ensure that the blower on the power supply is functioning properly. If not,
correct the blower condition and wait one minute.
3. If unable to correct the problem, contact your HP authorized service
representative.