Aisle space, Computer room unpacking space, Specify uncrating space – HP 9000 rp5400 Servers User Manual

Page 138: Electrical

background image

For service access, the server slides on rails 28" beyond the edge of the chassis in the front. An
additional minimum of 3' of workspace on all sides is required for servicing the server.

Aisle Space

The minimum aisle space between rows of installed HP rp54xx server/cabinets is 3 feet, front
and back, for airflow and serviceability.

Computer Room Unpacking Space

Specify Uncrating Space

rp54xx Systems are shipped in integrated cabinets on a 34.75" (88.25 cm.) x 26" (66 cm.) pallet.
The combined height of the packaged container and the pallets are as follows:

1.1 meter rack - 60 inches

1.6 meter rack - 73 inches

2.0 meter rack - 87 inches

Allow room (a circular area approximately 12 feet (3.5 meters) in diameter) for uncrating the
system and rolling the cabinet off the pallet on rails. Allow additional space for temporary storage
of the shipping containers and packing materials..

Electrical

The HP rp54xx power system is comprised of one, two or three autoranging, 12A/10A/5A, 930W
hot-swappable system power supplies, depending on how the system is configured. The maximum