OPERATION

6

91

OPTIFLEX 2200 C/F

www.krohne.com

07/2013 - 4000668002 - HB OPTIFLEX 2200 R02 en

Menu item 2.2.2 DIAGNOSTIC (Configuration mode / Supervisor menu) supplies more data. This
includes internal voltages, the loop current and the reset counter (watchdog timer). You can see
this data on the device display screen and in the DTM.

Types of error message

Figure 6-9: Status markers

1 Device status (NAMUR NE 107 symbols)
2 Symbol: Failure
3 Symbol: Function check
4 Symbol: Out of specification
5 Status marker line (marker 3 is shown)
6 When the status marker is on, a number is shown

NE 107 status

Type of

error

Description

Failure

Error

If an error message is shown in ERROR RECORD (menu item 1.3.1), the current output

goes to the error signal value set in menu item RANGE I (menu item 2.4.2) after the

time set in ERROR DELAY (menu item 2.4.5). For more data about menu items, refer to

Function description

on page 74.

Out of

specification

Warning

If a warning message is shown, there is no effect on the current output value.