3

INSTALLATION

26

OPTIFLEX 2200 C/F

www.krohne.com

07/2013 - 4000668002 - HB OPTIFLEX 2200 R02 en

3.6.3 Installation in standpipes (stilling wells and bypass chambers)

Use a standpipe if:

• The liquid is very turbulent or agitated.
• There are too many other objects in the tank.
• The device is measuring a liquid in a tank with a floating roof.

Figure 3-18: Installation recommendations for standpipes (stilling wells and bypass chambers)

1 Stilling well
2 Bypass chamber
3 Vent
4 Level of the liquid

INFORMATION!
Stilling wells are not necessary for devices with coaxial probes. But if there is a sudden change
in diameter in the stilling well, we recommend that you install a device with a coaxial probe.