TECHNICAL DATA

8

119

OPTIFLEX 2200 C/F

www.krohne.com

07/2013 - 4000668002 - HB OPTIFLEX 2200 R02 en

cFMus - Dual Seal-approved

- for 4...20 mA HART output

(pending for fieldbus options)

NEC 500 (Division ratings)

NEC 500 (Division ratings)

NEC 500 (Division ratings)

NEC 500 (Division ratings)

XP-AIS / Cl. I / Div. 1 / Gr. ABCD / T6-T1;

DIP / Cl. II, III / Div. 1 / Gr. EFG / T6-T1;

IS / Cl. I, II, III / Div. 1 / Gr. ABCDEFG / T6-T1;

NI / Cl. I / Div. 2 / Gr. ABCD / T6-T1

NEC 505 (Zone ratings)

NEC 505 (Zone ratings)

NEC 505 (Zone ratings)

NEC 505 (Zone ratings)

Cl. I / Zone 0 / AEx d [ia] / IIC / T6-T1;

Cl. I / Zone 0 / AEx ia / IIC / T6-T1;

Cl. I / Zone 2 / AEx nA / IIC / T6-T1;

Zone 20 / AEx ia / IIIC / T90°C

Zone 20 / AEx tb [ia] / IIIC / T90°C

Hazardous (Classified) Locations, indoor/outdoor Type 4X and 6P, IP66, Dual Seal

CEC Section 18 (Zone ratings)

CEC Section 18 (Zone ratings)

CEC Section 18 (Zone ratings)

CEC Section 18 (Zone ratings)

Cl. I, Zone 0, Ex d [ia], IIC, T6-T1;

Cl. I, Zone 0, Ex ia, IIC, T6-T1;

Cl. I, Zone 2, Ex nA, IIC, T6-T1

CEC Section 18 and Annex J (Division ratings)

CEC Section 18 and Annex J (Division ratings)

CEC Section 18 and Annex J (Division ratings)

CEC Section 18 and Annex J (Division ratings)

XP-AIS / Cl. I / Div. 1 / Gr. BCD / T6-T1

DIP / Cl. II, III / Div. 1 / Gr. EFG / T6-T1

IS / Cl. I / Div. 1 / Gr. BCD / T6-T1

NI / Cl. I / Div. 2 / Gr. ABCD / T6-T1

NEPSI

Ex ia IIC T2~T6 Gb or Ex ia IIC T2~T6 Ga/Gb DIP A20/A21 T

A

T90°C IP6X

Ex d ia IIC T2~T6 Gb or Ex d ia IIC T2~T6 Ga/Gb DIP A20/A21 T

A

T90°C IP6X

Other standards and approvals

Other standards and approvals

Other standards and approvals

Other standards and approvals

SIL

- only for 4...20 mA HART output

Compact version only: SIL 2 - certified according to all the requirements in

EN 61508 (Full Assessment) and for high/low demand mode operation. HFT=0,

SFF=94.3% (for non-Ex / Ex i devices) or 92.1% (for Ex d devices), type B device

EMC

EMC Directives 2004/108/EC in conjunction with EN 61326-1 (2006). The device

agrees with this standard if the time constant ≥ 3 seconds and:

- the device has a coaxial probe or

- the device has a single / double probe that is installed in a metallic tank. For more

data, refer to

Electromagnetic compatibility

on page 8.

SIL 2-approved devices agree with EN 61326-3-1 (2006) and EN 61326-3-2 (2006)

NAMUR

NAMUR NE 21 Electromagnetic Compatibility (EMC) of Industrial Process and

Laboratory Control Equipment

NAMUR NE 43 Standardization of the Signal Level for the Failure Information of

Digital Transmitters

NAMUR NE 53 Software and Hardware of Field Devices and Signal Processing

Devices with Digital Electronics

NAMUR NE 107 Self-Monitoring and Diagnosis of Field Devices

CRN

This certification is applicable for all Canadian provinces and territories. For more

data, refer to the website.

Construction code

On request: NACE MR0175 / ISO 15156; NACE MR0103

1 HART® is a registered trademark of the HART Communication Foundation
2 Only the 3.6 mA error signal is applicable to SIL-approved devices