Technical data – KROHNE OPTIFLEX 2200 C_F EN User Manual
Page 119
TECHNICAL DATA
8
119
OPTIFLEX 2200 C/F
www.krohne.com
07/2013 - 4000668002 - HB OPTIFLEX 2200 R02 en
cFMus - Dual Seal-approved
- for 4...20 mA HART output
(pending for fieldbus options)
NEC 500 (Division ratings)
NEC 500 (Division ratings)
NEC 500 (Division ratings)
NEC 500 (Division ratings)
XP-AIS / Cl. I / Div. 1 / Gr. ABCD / T6-T1;
DIP / Cl. II, III / Div. 1 / Gr. EFG / T6-T1;
IS / Cl. I, II, III / Div. 1 / Gr. ABCDEFG / T6-T1;
NI / Cl. I / Div. 2 / Gr. ABCD / T6-T1
NEC 505 (Zone ratings)
NEC 505 (Zone ratings)
NEC 505 (Zone ratings)
NEC 505 (Zone ratings)
Cl. I / Zone 0 / AEx d [ia] / IIC / T6-T1;
Cl. I / Zone 0 / AEx ia / IIC / T6-T1;
Cl. I / Zone 2 / AEx nA / IIC / T6-T1;
Zone 20 / AEx ia / IIIC / T90°C
Zone 20 / AEx tb [ia] / IIIC / T90°C
Hazardous (Classified) Locations, indoor/outdoor Type 4X and 6P, IP66, Dual Seal
CEC Section 18 (Zone ratings)
CEC Section 18 (Zone ratings)
CEC Section 18 (Zone ratings)
CEC Section 18 (Zone ratings)
Cl. I, Zone 0, Ex d [ia], IIC, T6-T1;
Cl. I, Zone 0, Ex ia, IIC, T6-T1;
Cl. I, Zone 2, Ex nA, IIC, T6-T1
CEC Section 18 and Annex J (Division ratings)
CEC Section 18 and Annex J (Division ratings)
CEC Section 18 and Annex J (Division ratings)
CEC Section 18 and Annex J (Division ratings)
XP-AIS / Cl. I / Div. 1 / Gr. BCD / T6-T1
DIP / Cl. II, III / Div. 1 / Gr. EFG / T6-T1
IS / Cl. I / Div. 1 / Gr. BCD / T6-T1
NI / Cl. I / Div. 2 / Gr. ABCD / T6-T1
NEPSI
Ex ia IIC T2~T6 Gb or Ex ia IIC T2~T6 Ga/Gb DIP A20/A21 T
A
T90°C IP6X
Ex d ia IIC T2~T6 Gb or Ex d ia IIC T2~T6 Ga/Gb DIP A20/A21 T
A
T90°C IP6X
Other standards and approvals
Other standards and approvals
Other standards and approvals
Other standards and approvals
SIL
- only for 4...20 mA HART output
Compact version only: SIL 2 - certified according to all the requirements in
EN 61508 (Full Assessment) and for high/low demand mode operation. HFT=0,
SFF=94.3% (for non-Ex / Ex i devices) or 92.1% (for Ex d devices), type B device
EMC
EMC Directives 2004/108/EC in conjunction with EN 61326-1 (2006). The device
agrees with this standard if the time constant ≥ 3 seconds and:
- the device has a coaxial probe or
- the device has a single / double probe that is installed in a metallic tank. For more
data, refer to
Electromagnetic compatibility
on page 8.
SIL 2-approved devices agree with EN 61326-3-1 (2006) and EN 61326-3-2 (2006)
NAMUR
NAMUR NE 21 Electromagnetic Compatibility (EMC) of Industrial Process and
Laboratory Control Equipment
NAMUR NE 43 Standardization of the Signal Level for the Failure Information of
Digital Transmitters
NAMUR NE 53 Software and Hardware of Field Devices and Signal Processing
Devices with Digital Electronics
NAMUR NE 107 Self-Monitoring and Diagnosis of Field Devices
CRN
This certification is applicable for all Canadian provinces and territories. For more
data, refer to the website.
Construction code
On request: NACE MR0175 / ISO 15156; NACE MR0103
1 HART® is a registered trademark of the HART Communication Foundation
2 Only the 3.6 mA error signal is applicable to SIL-approved devices