6

OPERATION

78

OPTIFLEX 2200 C/F

www.krohne.com

07/2013 - 4000668002 - HB OPTIFLEX 2200 R02 en

2.7.0 DISPLAY

2.7.1

LANGUAGE

Data can be shown in any of the languages

stored in the device.

9 languages are

available in 3 packs:

(1) English, French,

German and Italian;

(2) English, French,

Spanish and

Portuguese; (3) English,

Chinese (Simplified),

Japanese and Russian

3

2.7.2

LENGTH UNIT

The length unit of measurement shown in

normal mode.

m, cm, mm, in (inches),

ft (feet)

m

2.7.3

CONV UNIT

Conversion unit. The length, volume or

mass conversion unit for the conversion

table and shown in normal mode.

kg, t, Ston, Lton, m, cm,

mm, in, ft, m3, L, gal,

Imp, ft3, bbl

kg

2.7.4

PSWD YES/NO

If it is necessary to protect your settings in

the supervisor menu with a password, set

this menu item to YES

YES

YES

YES.

YES, NO

YES

2.7.5

PASSWORD

This changes the password for the

supervisor menu. Push the buttons up to 6

times in any order. This will be the new

password. To confirm the change, enter

the new password a second time. For

more data, refer to

Protection of the

device settings

on page 83.

[>>>>], [^

^

^

^], [

],

[

], [>>>>] and [^

^

^

^]

2.7.6

CONTRAST

The contrast control for the display

screen. You can select a shade of grey

between light grey (level 20) and black

(level 54).

min-max: 20…54

36

2.8.0 CONV. TABLE

2.8.1

INPUT TABLE

The device uses a conversion table

(strapping table) to convert

measurements to volume and mass

readings. The readings are shown in

normal mode. Go to this menu item and

enter the entry number (01...30). Then

enter the level and the related volume /

mass / flow rate value for that entry. Push

[^

^

^

^] to confirm the entry values. Continue

the procedure until the device has data for

all the entries. For more data, refer to

How to configure the device to measure

volume or mass

on page 85.

min. 2 entries

max. 30 entries

(level / volume or mass)

0 entries

2.8.2

DELETE TABLE

This menu item erases the data in the

conversion table.

YES, NO

NO

2.9.0 CONFIG/RESET

2.9.1

SAVE

This menu item is not available.

YES, NO

NO

2.9.2

RECALL

This menu item is not available.

YES, NO

NO

2.9.3

RESTART

This menu item starts the device again.

YES, NO

NO

2.9.4

RESET FACT.

If you set this menu item to "YES", the

device goes back to its initial settings (set

by the manufacturer in the factory).

YES, NO

NO

1 Units and range depend on the output function, length unit and volume unit selected
2 Refer to the table that follows (Default values for menu items 2.4.3 SCALE 4mA and 2.4.4 SCALE 20mA)
3 If the device has the LCD display option, this depends on data given in the customer order

Menu
No.

Function

Function description

Selection list

Default