Operation – KROHNE OPTIFLEX 2200 C_F EN User Manual
Page 78
6
OPERATION
78
OPTIFLEX 2200 C/F
www.krohne.com
07/2013 - 4000668002 - HB OPTIFLEX 2200 R02 en
2.7.0 DISPLAY
2.7.1
LANGUAGE
Data can be shown in any of the languages
stored in the device.
9 languages are
available in 3 packs:
(1) English, French,
German and Italian;
(2) English, French,
Spanish and
Portuguese; (3) English,
Chinese (Simplified),
Japanese and Russian
3
2.7.2
LENGTH UNIT
The length unit of measurement shown in
normal mode.
m, cm, mm, in (inches),
ft (feet)
m
2.7.3
CONV UNIT
Conversion unit. The length, volume or
mass conversion unit for the conversion
table and shown in normal mode.
kg, t, Ston, Lton, m, cm,
mm, in, ft, m3, L, gal,
Imp, ft3, bbl
kg
2.7.4
PSWD YES/NO
If it is necessary to protect your settings in
the supervisor menu with a password, set
this menu item to YES
YES
YES
YES.
YES, NO
YES
2.7.5
PASSWORD
This changes the password for the
supervisor menu. Push the buttons up to 6
times in any order. This will be the new
password. To confirm the change, enter
the new password a second time. For
more data, refer to
Protection of the
device settings
on page 83.
[>>>>], [^
^
^
^], [
],
[
], [>>>>] and [^
^
^
^]
2.7.6
CONTRAST
The contrast control for the display
screen. You can select a shade of grey
between light grey (level 20) and black
(level 54).
min-max: 20…54
36
2.8.0 CONV. TABLE
2.8.1
INPUT TABLE
The device uses a conversion table
(strapping table) to convert
measurements to volume and mass
readings. The readings are shown in
normal mode. Go to this menu item and
enter the entry number (01...30). Then
enter the level and the related volume /
mass / flow rate value for that entry. Push
[^
^
^
^] to confirm the entry values. Continue
the procedure until the device has data for
all the entries. For more data, refer to
How to configure the device to measure
volume or mass
on page 85.
min. 2 entries
max. 30 entries
(level / volume or mass)
0 entries
2.8.2
DELETE TABLE
This menu item erases the data in the
conversion table.
YES, NO
NO
2.9.0 CONFIG/RESET
2.9.1
SAVE
This menu item is not available.
YES, NO
NO
2.9.2
RECALL
This menu item is not available.
YES, NO
NO
2.9.3
RESTART
This menu item starts the device again.
YES, NO
NO
2.9.4
RESET FACT.
If you set this menu item to "YES", the
device goes back to its initial settings (set
by the manufacturer in the factory).
YES, NO
NO
1 Units and range depend on the output function, length unit and volume unit selected
2 Refer to the table that follows (Default values for menu items 2.4.3 SCALE 4mA and 2.4.4 SCALE 20mA)
3 If the device has the LCD display option, this depends on data given in the customer order
Menu
No.
Function
Function description
Selection list
Default