beautypg.com

Electrical connections – KROHNE OPTIFLEX 2200 C_F EN User Manual

Page 52

background image

4

ELECTRICAL CONNECTIONS

52

OPTIFLEX 2200 C/F

www.krohne.com

07/2013 - 4000668002 - HB OPTIFLEX 2200 R02 en

4.3.2 How to prepare a signal cable supplied by the customer

Figure 4-6: Equipment needed to prepare the signal cable

1 Signal cable (supplied on request)
2 2 heat-shrinkable sleeves for the PVC jacket (not supplied)
3 8 ferrules for the end of the conductors (not supplied)
4 2 Faston connectors for the shield wires
5 Shield wire insulation, 2 sleeves
6 Wire stripper (not supplied)
7 Crimping pliers (not supplied)

INFORMATION!

The Faston connector for the stranded drain wire must agree with DIN 46 228: E 1.5-8

The wire end ferrules for the twisted pair of conductors must agree with DIN 46 228: E 0.5-8