3.6 Installation recommendations for liquids

3.6.1 General requirements

Clearance between the probe and other objects in the tank

Figure 3-11: Installation recommendations for liquids

1 The electromagnetic (EM) field generated by the device. It has a radius of R

min

. Make sure that the EM field is clear of

objects and product flow. Refer to the table that follows.

2 If there are too many objects in the tank, install a bypass chamber or stilling well.
3 Keep the probe straight. If the probe is too long, shorten the probe length. Make sure that the device is configured with

the new probe length. For more data on the procedure, refer to

How to decrease the length of probes

on page 89.

4 Empty space. Refer to the table that follows.

Probe type

Empty space (radius, R

min

), around the probe

[mm]

[inches]

Coaxial

0

0

Double rod / cable

100

4

Single rod / cable

300

12